ItemPXZ20K-500PXZ20K-1000PXZ20K-1500
OVP (Over Voltage Protection)Protective operationLoad off, indicate “OVP” on the display. SLV OVP is displayed on the slave unit.
Setting range50 V to 550 V100V to 1100V150 V to 1650 V
Setting accuracy±(0.1 % of setting + 0.2 % of rating)
Resolution0.05 V0.1 V0.1 V
OCP (Over Current Protection)Protective operationLoad off, indicate “OCP” on the display. SLV OCP is displayed on the slave unit.
Setting range12 A to 132 A6A to 66A3 A to 33 A
Setting accuracy±(0.75 % of rating)
Resolution0.01 A0.005A0.002 A
OPP (Over Power Protection)Protective operationLoad off, indicate “OPP” on the display. SLV OPP is displayed on the slave unit.
Setting range2 kW to 24 kW
Setting accuracy±(1.0 % of power rating + 1.0 % of current rating × Vin)
Resolution2 W
UVP (Under Voltage Protection)Protective operationLoad off, indicate “UVP” on the display. SLV UVP is displayed on the slave unit.
Setting range0 V to 500 V0V to 1000V0 V to 1500 V
SelectableEnable/Disable
Setting accuracy±(0.1 % of setting + 0.2 % of rating)
Resolution0.05 V0.1 V0.1 V
Watchdog Alarm (Communication error protection)Protective operationLoad off, indicate “WDOG” on the display
Setting range1 s to 3600 s
SelectableEnable/Disable
External Alarm LOW Level (external input alarm detection)Protective operationLoad off, indicate “EXT LOW” on the display

Related specifications : PXZシリーズ