Item/Model | PWX1500L | PWX1500ML | PWX1500MH | PWX1500H |
---|
Environmental conditions | Operating environment | Indoor use, overvoltage category II |
---|
Operating temperature/ humidity | 0 °C to +50 °C (32 °F to +122 °F)/ 20 %rh to 85 %rh (no condensation) |
---|
Storage temperature/ humidity | -10 °C to +60 °C (14 °F to +140 °F)/ 90 %rh or less (no condensation) |
---|
Altitude | Up to 2000 m |
---|
Cooling method | Forced air cooling using fan |
---|
Grounding polarity | Negative grounding or positive grounding possible |
---|
Isolation voltage | | ± 250 Vmax | ± 500 Vmax | ± 800 Vmax |
---|
Isolated analog interface *1 | ± 60 Vmax |
---|
Withstanding voltage | Between input and FG | No abnormalities when 1500 Vac is applied for 1 minute |
---|
Between input and output | No abnormalities at 2000 Vac for 1 minute | No abnormalities at 2250 Vac for 1 minute |
---|
Between output and FG | No abnormalities at 1500 Vdc for 1 minute | No abnormalities at 1600 Vac for 1 minute | No abnormalities at 2000 Vdc for 1 minute |
---|
Between input and Isolated Analog Interface *1 | No abnormalities at 2650 Vac for 1 minute |
---|
Between output and Isolated Analog Interface *1 | No abnormalities at 2300 Vdc for 1 minute | No abnormalities at 2650 Vac for 1 minute | No abnormalities at 3300 Vac for 1 minute |
---|
Insulation resistance | Between input and FG | 500 Vdc, 100 MΩ or more (70 % or less) |
---|
Between input and output | 500 Vdc, 100 MΩ or more (70 % or less) | 1000 Vdc, 100 MΩ or more (70 % or less) |
---|
Between output and FG | 500 Vdc, 40 MΩ or more(70 % or less) | 1000 Vdc, 40 MΩ or more (70 % or less) |
---|
Safety | Conforms to the requirements of the directive and standard below.
Low Voltage Directive 2014/35/EU *3
EN 61010-1 (Class I *6, Pollution degree 2 *7) |
---|
Electromagnetic compatibility (EMC) | Conforms to the requirements of the directive and standard below.
EMC Directive 2014/30/EU
EN 61326-1 (Class A4)
EN 55011 (Class A*4, Group 1 *5)
EN 61000-3-2、EN 61000-3-3
Applicable under the following conditions The maximum length of all cabling and wiring connected to the PWX must be less than 3 m. |
---|
Dimensions (maximum)/Weight | 422.8(485) W×43(44) H×500(580) Dmm/Approx. 9.5 kg (20.94 lb) | 422.8(485) W×43(44) H×500(580) Dmm/Approx. 9 kg (19.84 lb) |
---|
Accessories | Output terminal cover: 1 pc., Input terminal cover set, Output terminal M8 bolt set: M8 bolts ×2 sets(Bolt, nut, spring washer, and washer for each bolt), Chassis connection wire: 1 wire, J1 connector plug kit: 1 set(Housing: 1 pc., Connector: 1 pc., Plug: 1 pc., Strain relief: 1 pc., Clips: 2 pcs., and two types of Screws: 2 pcs.,), Packing list: 1 copy, Quick reference (1 each for English and Japanese), Safety precautions: 1 copy, China RoHS sheet: 1 copy, CD-ROM: 1 disc |
---|
*1 Factory option. *2 Does not apply to specially ordered or modified PWXs. *3 Limited to products that have the CE/UKCA marking on their panels. Not be in compliance with EMC limits unless the ferrite core is attached on the cable for connection of J1 connector. *4 This is a Class A equipment. The PWX is intended for use in an industrial environment. This product may cause interference if used in residential areas. Such use must be avoided unless the user takes special measures to reduce electromagnetic emissions to prevent interference to the reception of radio and television broadcasts. *5 This is a Group 1 equipment. The PWX does not generate and/or use intentionally radio-frequency energy, in the from of electromagnetic radiation, inductive and/or capacitive coupling, for the treatment of material or inspection/analysis purpose. *6 This is a Class I equipment. Be sure to ground the PWX’s protective conductor terminal. The safety of this product is only guaranteed when the product is properly grounded. *7 Pollution is addition of foreign matter (solid, liquid or gaseous) that may produce a reduction of dielectric strength or surface resistivity. Pollution Degree 2 assumes that only non-conductive pollution will occur except for an occasional temporary conductivity caused by condensation.